Vehicular and Mechanical Equipment Near Overhead Power Lines

Electrical Equipment/Machinery

GFCI Protection

Table I:
Approach Distance For Qualified Employees

Vehicular and Mechanical Equipment Near Overhead Power Lines

Overhead power lines will be de-energized and grounded before any work is performed by any vehicle or mechanical equipment near the energized overhead power lines. If the overhead lines can not be de-energized, then the vehicle or mechanical equipment will be operated so that a clearance of 10 feet is maintained. If the voltage of the overhead line exceeds 50 kV, the distance will be increased 4 inches for every 10 kV increase in power. If lines are protected with properly rated insulating devices, the distance may be decreased. If the equipment is an aerial lift insulated for the voltage involved and if the work is performed by a Qualified Person, the clearance may be reduced to a distance given in Table I. If protective measures such as guarding or isolation are provided, these measures must protect the employee from contacting such lines directly with any part of the body or indirectly through conductive materials, tools, or equipment.